Extra Flexible Plenum Cables/Two Conductors-Shielded CMP/CL2P LOW-Smoke PVC Insulation and Jacket Conductor: Bunched strand annealed bare copper Insulation: Low smoke PVC color coded Cable: conductors twisted or cabled aluminum polyester shield tinned copper drain wire Jacket: Low smoke PVC white temperature range -20 to +60C Packaging: Spools or reels REELEX boxes Application: FOR USE IN AIR PLENUMS FOR INTERCOM SYSTEM SECURITY ENERGY MANAGEMENT
Part No. |
No. of corns |
AWG size |
Conr. Strand &coating |
Nominal Insulation thickness |
Nominal jacket thickness |
Nominal outer diameter |
Nominal capaci- tance |
Weight LBS/ 1000FT |
inches |
mm |
inches |
mm |
inches |
mm |
DZ332160 |
1pair |
22 |
7/30bare |
.008 |
.20 |
.015 |
.38 |
.125 |
3.18 |
50 |
12 |
DZ332170 |
1pair |
20 |
7/28bare |
.008 |
.20 |
.015 |
.38 |
.145 |
3.68 |
55 |
16 |
DZ332180 |
1pair |
18 |
7/26bare |
.008 |
.20 |
.015 |
.38 |
.165 |
4.19 |
60 |
24 |
DZ332190 |
1pair |
16 |
19/29bare |
.013 |
.33 |
.015 |
.38 |
.210 |
5.33 |
55 |
34 |
+DZ332200 |
1pair |
14 |
19/27bare |
.013 |
.33 |
.015 |
.38 |
.240 |
6.10 |
55 |
45 |
+DZ332210 |
1pair |
12 |
19/25bare |
.013 |
.33 |
.015 |
.38 |
.295 |
7.49 |
55 |
65 |
Nylon rip cord under jacket +CL2P only UL defines CMP as 26 to 16 AWG Capacitance: (pt/ft) * Mutual (conductor to conductor) ** One conductor and others connected to shield Standard Box or Reel Size: 1000ft Standard Jacket Color: White Color Code: 1 Black 2 red 3 white 4 green 5 brown 6 blue 7 orange 8 yellow 9 purple 10 gray 11 pink 12 tan 13 -wht/blk 14 -wht/red 15 wht/grn Drain Wire: CONRS SIZE DRAIN SIZE 22AWG 22 7/30 20AWG 22 7/30 18AWG 20 7/28 16AWG 18 7/26 14AWG 16 19/29 12AWG 14 19/27 |